Options/Accessories
6.6.1 Connecting Isolation Transformer
| Isolation | UPS | 
 | External | External | 
 | External | External | External | ||
| Transformer | 
 | 
 | Input Fuses* | Input Cable | 
 | PE Cable | Output | Temp. | ||
| 
 | 
 | 
 | FM [A] | [mm2] | 
 | [mm2] | Cable | Signal Cable | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | [mm2] | [mm2] | ||
| 280kVA | 240kVA | 500 | 
 | 2//125 | 
 | 100 | 
 | 2//125 | 2 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| *DIN gL types | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| PVC cables insulated to withstand a maximum ambient temperature of 30oC | 
 | |||||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| Isolation | UPS | 
 | External | 
 | External | External PE | 
 | External | External | |
| Transformer | 
 | 
 | Input | 
 | Input Cable | 
 | Cable | 
 | Output | Temp. Signal | 
| 
 | 
 | 
 | Fuses* FM | 
 | [mm2] | 
 | [mm2] | 
 | Cable | Cable | 
| 
 | 
 | 
 | [A] | 
 | 
 | 
 | 
 | [mm2] | [mm2] | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 370kW | 320kVA | 
 | 630 | 
 | 2//200 | 150 | 
 | 2//200 | 2 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
*DIN gL types
PVC cables insulated to withstand a maximum ambient temperature of 30°C
| 62 | Installation Guide APC Silcon  | 