American Power Conversion AP9604S Options/Accessories, Service Bypass Panel for Single Operation

Models: AP9604S

1 73
Download 73 pages 10.24 Kb
Page 42
Image 42

Options/Accessories

6.0 Options/Accessories

Please contact your local APC representative for information on options/accessories available in your region. See “How to Contact APC” in this guide.

6.1Service Bypass Panel for Single Operation

UPS

Exter-nal

Max.

System

System

Max.

Max.

Dimensions

Weight

Fixing

 

System

Prospec-

Input/

Output/

External

Cable

HxWxD [mm]

[kg]

Cen-

 

Input

tive

UPS

UPS

System

Size/

 

 

tres

 

Fuse

Short-

Input

Output

Output

Stud

 

 

AxB

 

[A]

Circuit

Cable

Cable

Fuse

Size

 

 

[mm]

 

 

Current

[mm2]

[mm2]

[A]***

 

 

 

 

 

 

[kA]

**

**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240kW

500

45

2x125

2x100

400

M12

?

?

 

 

 

 

 

 

 

 

 

 

?

320kW

630

45

2x200

2x150

500

M12

?

***If no external System Output fuses are available or if it has a higher value than indicated above, System Output and UPS Output cables should be dimensioned as System Input and UPS Input cables.

**Sizes according to IEC 364-5-532 for PVC insulated copper cables (max. ambient temperature: 30oC). Installation method B: Insulated conductors in wall conduit.

Also refer to local legal regulations.

Beware that single-phase Switch Mode Power supply loads will increase neutral current! At a 100% SMPS load, neutral cable should be dimensioned for 200% of phase current.

*Depth of enclosure includes switch handles

990-4056

42

Installation Guide APC Silcon 240-320kW 400V UPS

Page 42
Image 42
American Power Conversion AP9604S manual Options/Accessories, Service Bypass Panel for Single Operation