2.5.3Battery Test Function

Input

Description

Location

Battery Test

Front panel momentary push button. Push and hold drops

Push button mounted on

 

output volts to 45Vdc. This is below battery float voltage and

controller front panel.

 

is used to check the batteries can supply the system load.

 

2.5.4Enable Function

Input

Description

Location

Enable

Back-plane circuit board mounted 3-way Molex header. Link

SK22 (mounted on back-

 

pins 1 and 2 with supplied link for “local” enable of rectifier

plane board).

 

outputs. Link pins 2 and 3 for “remote” enable.

 

 

If “remote” enable SK17-1 and SK17-6 must be linked to

 

 

enable rectifier outputs.

 

 

System is set to “Local Enable” as standard

 

SK17

SK22

Note: Prior to accessing and making connections ensure batteries are disconnected from the system by setting battery connection switch to “OFF” via controller / alarm card front panel (see section 2.3) and by turning the external battery breaker off.

The AC input supply must then be turned off by operating the local isolator or disconnection device.