4.2.34 Circuit Breakers Rear Access

DISTRIBUTION

CONTROLLER

12

3 4

No. of Outputs :

4

Output Rating :

4 O/P’s up to 20A max

 

2 O/P’s up to 40A max

Circuit Breakers :

1 O/P up to 50A max

Series DC Current trip,

Trip Alarm :

Medium time delay.

YES

Remove the rear cover to give access to the output terminals (shown below).

To connect to the output terminals use M4 ring crimps with cables rated to at least the same current rating as the corresponding output breaker and colour coded as to meet all the local installation regulations.

Cables should be routed through knockout panels in rear cover or in the side of the shelf itself.

Output 1

Top 4 Terminals :

0V / Earth, when output earthed

Output 4

Distributed Output 1

Bottom 4 Terminals :

+ 54Vdc when negative earth - 54Vdc when positive earth

Distributed Output 4

User Manual 990-9178A

Page 34 of 44

18th FEB 02

DC MX06 40A Shelf

Page 34
Image 34
American Power Conversion DC Series user manual 3 4 Circuit Breakers Rear Access