4.2.34 Circuit Breakers Rear Access
DISTRIBUTION | CONTROLLER |
12
3 4
No. of Outputs : | 4 |
Output Rating : | 4 O/P’s up to 20A max |
| 2 O/P’s up to 40A max |
Circuit Breakers : | 1 O/P up to 50A max |
Series DC Current trip, | |
Trip Alarm : | Medium time delay. |
YES |
•Remove the rear cover to give access to the output terminals (shown below).
•To connect to the output terminals use M4 ring crimps with cables rated to at least the same current rating as the corresponding output breaker and colour coded as to meet all the local installation regulations.
Cables should be routed through knockout panels in rear cover or in the side of the shelf itself.
Output 1
Top 4 Terminals :
0V / Earth, when output earthed
Output 4
Distributed Output 1
Bottom 4 Terminals :
+ 54Vdc when negative earth - 54Vdc when positive earth
Distributed Output 4
User Manual | Page 34 of 44 | 18th FEB 02 |
DC MX06 40A Shelf |