4.2 DC Distribution
The MX06 40A Shelf has a DC distribution module fitted. This module contains the chosen distribution components of either circuit breakers or fuses. It also contains an LVD contact (controlled by the controller) and a current shunt measuring load current. The modules can be configured for either positive or negative earthed output. The output can also be left floating to facilitate external grounding. A tripped output will give an alarm displayed as a front panel LED.
There are three standard distribution component types:
1/ 10 GMT Fuses
2/ 4 Cartridge Fuses
3/ 4 Circuit Breakers
As explained earlier all three types are offered with either front or rear cable access giving six modules types.
4.2.110 GMT Fuses Rear Access
DISTRIBUTION
1
2
3
4
5
FUSES
6
7
8
9
10
No. of Outputs : | 10 max |
Output Rating : | 10A max per output |
Fuses : | (42A total) |
Trip Alarm : | YES |
•Cables should be rated to at least the same current rating as the corresponding output fuse and be colour coded as to meet all the local installation regulations.
•To attach the cables remove the rear cover for access to output connectors.
•Simply strip the ends of the cables and screw into output terminal block.
Output 1
Top Connector :
Common (0V Return) / Earth (if link fitted)
Output 10
Distributed Output 1
Bottom Connector :
- 54Vdc (when positive earthed)
Distributed Output 10