4.4.4Battery Connection Diagram
Earth connection for grounding output
Battery Positive
Earth Stud
Battery Negative
4.5 System Output Earthing
The MX06 40A Shelf has its output earthed as default. The output is earthed by the earth cable joining the earth stud to the output earthing
The default configurations are as follows:
54 V systems are set to earthed positive output
27 V systems are set to earthed negative output
User Manual | Page 40 of 44 | 18th FEB 02 |