2.4 Alarms

2.4.1Available Alarms

To monitor the system status a selection of alarm outputs are available. Dependant upon the rectifiers fitted either 4 front panel LED’s or a single LED give visual notification of a system fault. There is also a range of open collector transistor alarm outputs, which can be accessed at the rear of the shelf or on a front panel connector (selected models). Finally there are 2 sets of relay contacts that can be configured to represent 1 or more alarms selected by the user.

Below is a list of the available alarms along with their function and pin number.

Note/ Alarms marked with a * are not available if system is fitted with single LED rectifiers.

Alarm / User

Description

Rear

Front

Outputs

 

Access

Access

Bus Voltage Low

System volts dropped to LVD set level +10%, LVD imminent

SK14-2

SK4-25

* Fan Fail

 

One or more of the Rectifier fans have stopped

SK14-3

SK4-24

2+ Rectifiers Fail

2 or more rectifiers giving output less than 31Vdc

SK14-4

SK4-5

Rectifier Fail

1 Rectifier giving output less than 31Vdc

SK14-5

SK4-6

Distribution Trip

1 or more fuse blown or breaker tripped

SK14-6

SK4-2

AC Fail

 

1 or more of the AC input feeds failed

SK14-7

SK4-1

* Over Current

1 or more rectifiers in current limit state

SK14-8

SK4-23

* Over Voltage

1 or more rectifiers tripped due to excessive o/p voltage

SK14-9

SK4-22

 

 

(interrupt AC input or remove rectifier and refit to reset)

 

 

* Over Temperature

1 or more rectifiers tripped due to excessive internal

SK14-10

SK4-21

 

 

temperatures (resets itself when cooled down)

 

 

Signal Common

Use to reference all alarms to

SK17-1

SK4-17

Current Share

Use for paralleling purposes only

SK17-3

SK4-16

Current Analogue

Analogue voltage representing load current (1V = 5A ± 5%)

SK17-4

SK4-19

5V Auxiliary

Low current capability 5V supply for use with current limit

SK17-5

SK4-15

 

 

programming.

 

 

Major Failure

‘Minor’ relay contact (closed for alarm)

SK18-1

SK4-11

‘Minor’ relay contact (Common)

SK18-2

SK4-10

‘Minor’ relay contact (open for alarm)

SK18-3

SK4-12

Minor Failure

‘Major’ relay contact (closed for alarm)

SK18-4

SK4-8

‘Major’ relay contact (Common)

SK18-5

SK4-7

‘Major’ relay contact (open for alarm)

SK18-6

SK4-9

Warning! All alarm outputs other than the relay contacts are open collector transistors. Each output has a max voltage rating of 60Vdc and a current sink capability of 20mA