Install the adapter in a drop ceiling

Install the adapter in a drop ceiling

Use the ceiling adapter to provide an intake and exhaust outlet for the condenser.

Note: Allow at least 305 mm (12 in) of open space above the ceiling adapter opening so exhaust air is not blocked.

1. Determine a location to install the ceiling adapter.

2. Remove the ceiling tile in the chosen location and save it for a future step.

3. Place the ceiling adapter into the ceiling tile grid.

na0373a

4.Secure the ceiling adapter to the building structural

support (not the drop ceiling), using 10-gauge (minimum) steel wire.

na0397aManual backgroundManual backgroundManual backgroundManual backgroundManual background

5.When using 2 x 4 ft ceiling tiles, insert a cross member (not provided) for added support.

na0394a

NetworkAIR ACPA4000

9

Page 17
Image 17
APC manual Install the adapter in a drop ceiling, NetworkAIR ACPA4000