Drain Line

Drain Line

The equipment contains an on-board condensate pump for automatic condensate removal.The equipment ships with 15.24 m (50 ft) of hose and a quick-connect fitting for removing condensate. You can attach a different hose to the equipment if you follow these requirements:

You must use a 6-mm (1/4-in) outside diameter (OD), clear, polyurethane hose.

The hose length must not exceed 15.24 m (50 ft), and 4.88 m (16 ft) vertical maximum.

You must cut off all excess drain line and avoid kinking or pinching the drain line.

Connect the fitting to the drain line.

1.Insert the drain hose through the capture nut .

2.Push the drain hose over the barbs at the rear of the quick-connect fitting .

3.Screw the capture nut onto the quick-connect fitting .

Attach the drain line. Attach

the connector end of the hose to the drain line connector on the rear of the equipment and run the hose to a drain.

Detach the drain line. Press the quick- release button on the top of the drain line connector and remove the hose.

Note: The equipment does not drain unless the drain line is installed.

na2658a

Connect the fitting to the drain line.Attach the drain line. Attachna0319a

NetworkAIR ACPA4000

11

Page 19
Image 19
APC ACPA4000 manual Drain Line, Connect the fitting to the drain line, Attach the drain line. Attach