Operating schedules

Operating schedules

Path: Main Menu > Setup > Operating Schedule. Program up to eight sets of environmental controls that run according to the time and day.

Scheduling: on/off. Select Off to use the default schedule, or On to use the programmed schedules.

Reset schedules. Turn all schedules off and reset them to their factory default settings.

Edit schedules. Set the cooling options for up to eight time periods.

Schedule: 1 of 8

Select a schedule to modify.

Schedule: On/Off

Activate or deactivate this schedule.

Mode

Choose Cool, Vent Only, or System Off. See “Mode” on page 20.

Set Point

Set the target temperature for the room. See “Set Point” on

 

page 20.

Blower

Set the speed of the blower to High or Low. Use the Low blower

 

speed to remove humidity from the room air.

Day

Choose the days for this schedule to run. Options include: Every

 

day, Weekdays, Weekends, Sun, Mon, Tue, Wed, Thu, Fri, and

 

Sat.

Start Time

Set the time when this schedule becomes active. Times are entered

 

using a 24-hour clock.

Stop Time

Set the time when this schedule becomes inactive. Times are

 

entered using a 24-hour clock.

Note: If schedules overlap, the schedule with the highest day-priority runs. The priority is:

• Highest: Sun, Mon, Tue, Wed, Thu, Fri, Sat

Next Highest: Weekdays, Weekends

Lowest: Every Day

NetworkAIR ACPA4000

21