Clean the condenser filter and test the LCDI plug

Clean the condenser filter and test the LCDI plug

The condenser filter traps large items that may fall into the ducts. Periodically check and clean the filter to prevent damage to the condenser. While power is off, test the LCDI plug for proper operation.

1.Turn off the equipment and unplug it from its electrical outlet.

2. Remove the condenser air intake duct from the back of the equipment.

3. Clean the filter (inside the air intake duct) using your hand or a dry cloth.

Caution: To avoid equipment damage, do not test the LCDI plug while the equipment is operating.

na0311a

4.

Press the TEST button on the LCDI plug. The

RESET button

 

TEST button

 

POWER LED should go off.

 

POWER LED

5.

Press the RESET button on the LCDI plug. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER LED should come on.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

na2472a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clean the cabinet

Turn off the equipment and unplug it from its electrical outlet. Use a moist rag to wipe down the cabinet.

Caution: Do not clean the surface with thinners, alcohol, polishing powder, alkaline detergent, acid, or an abrasive brush. Using these items will damage the cabinet.

Update the main control board firmware

Occasionally, new firmware becomes available which may add new features. Firmware is available for download through the APC software/firmware downloads page, www.apc.com/tools/dowload.

You will need a computer with a serial port, a null modem serial cable, and a terminal emulation program that can use the xmodem protocol.

See “How to download firmware” on page 25.

NetworkAIR ACPA4000

37

Page 45
Image 45