Alarm Message | Action Required | |
|
| |
Remote temperature | Alarm setpoint may be too low. | |
high | Check the sensor placement. Ensure that the sensor is able to sense the | |
| ||
| cool supply air from the unit. | |
| Check that the sensor is not near a direct heat source such as an | |
| equipment discharge fan, a room supply duct, a window, direct sunlight, | |
| or a room entrance. | |
| Equipment capacity may be too small for room load. | |
| Check that the equipment is cooling. Verify that there is at least an 8°C | |
| (15°F) temperature difference between supply and return air. | |
|
| |
Remote temperature | Alarm setpoint may be too high. | |
low | Verify that the return air is not coming from a cold air supply source such | |
| ||
| as a room discharge duct or an open window. | |
|
| |
Remote humidity high | Alarm setpoint may be too low. | |
| Alarm delay may be too short. Allow sufficient time to let the equipment | |
| bring space humidity under control. This is especially true with new | |
| equipment | |
| Remote sensor may be located near a moisture source such as an open | |
| sink, a window, or an entrance to an unconditioned space. | |
| Equipment capacity may be too large for space. Reduce fan speed to low. | |
|
| |
Remote humidity low | Alarm setpoint may be too high. | |
|
| |
Air filter clogged | Change the filter. | |
|
| |
Water collection pan | Check the drain line for kinks, blockages, excessive length, or excessive | |
full | lift. | |
| Check the drain line connection on the rear of the unit for proper | |
| connection. Ensure the quick connect fitting is inserted and locked into | |
| the unit drain connection. | |
|
| |
User contact 1 alarm | Check the connected device. | |
|
| |
User contact 2 alarm | Check the connected device. | |
|
| |
User contact 3 alarm | Check the connected device. | |
|
| |
Equipment shutdown | Verify remote stop. | |
via remote stop | ||
| ||
|
|
32 | NetworkAIR ACPA4000 |