Output and downstream breakers
Q2, Q4, Q6
Duration [S] | Current [A] | Total load [%] | Event/Operation |
|
|
|
|
< 0.005 | 22 kA | Internal fault clearing. | |
|
|
|
|
60 | 3464* | 200 | Overload |
|
|
|
|
600 | 2165* | 125 | Overload |
|
|
|
|
∞ | 1732 | 100 | |
|
|
|
|
* In the absence if a coordination study conducted by a professional engineer, the recommended
instantaneous trip setting for breakers Q1, Q2, Q4, Q5, and Q6 is 22 kA
** Only applicable to Q2 and Q4
In the absence of a proper breaker coordination study and if only the actual Ip on the unit’s input terminals is known, this table must be used to optimize the instantaneous trip setting or to choose a breaker with a usable fixed instantaneous trip value.
Ip* [kA] | I peak | I setting [kA] |
|
|
|
200 | 16 | 18 |
|
|
|
140 | 14 | 16 |
|
|
|
100 | 13 | 15 |
|
|
|
50 | 10.5 | 12 |
|
|
|
30 | 9 | 11 |
|
|
|
* Ip = Abridgment for Prospective
This is the current that would flow in the fault circuit is the fuse was
replaced by a link with an infinitely small impedance
22 kA is the maximum peak
The instantaneous trip setting calculated by a professional engineer in a breaker coordination study must not disable the functionality of clearing and surviving an internal fault unless there is a written agreement between APC by Schneider Electric and the customer.
By ensuring the unit’s fault clearing ability (survival skills) i.e. using the correct instantaneous trip settings in the switch gear (installation), maximum power availability in normal operation is obtained for the critical load.
Note: The instantaneous trip setting can be calculated when utility Ip is known. An incorrect trip setting can result in limiting the system functionality and jeopardize the load support.
Symmetra MW II 1200 kW 3 x 400/230 V Installation - | 21 |