AC Input

AC Input

Input rating

1200 kW/kVA

Power Factor

1

Input Voltage

380 V

Input Frequency

50 Hz

Nominal input current (note 1)

1698 A

Input Current Limitation (note 2)

2133 A

Input Voltage

400 V

Input Frequency

50 Hz

Nominal input current (note 1)

1793 A

Input Current Limitation (note 2)

2200 A

Input Voltage

415 V

Input Frequency

50 Hz

Nominal input current (note 1)

1728 A

Input Current Limitation (note 2)

2170 A

 

 

DC Input

DC Input

Nominal Voltage (note 3)

2 x 384 V

INom Discharge (note 4)

1628 A

IMax Discharge (note 5)

1929 A

Caution: Over-current protection for the battery circuit is required by code. The minimum DC voltage rating of the battery supply over-current protection device is 500 V.