APC MW II manual Dual Mains Installation

Models: MW II

1 40
Download 40 pages 1.18 Kb
Page 26
Image 26

Note: The instantaneous trip setting must not be derated even though the UPS system is derated in system output power. The system size has no influence on the instantaneous trip setting.

Note: For derated systems, the APC Application Team can provide the correct breaker settings and breaker frame sizes.

Note: For upstream breakers not mentioned in the table, the APC Application Team can provide the correct breaker settings for on-line, overload, and trip currents.

The following diagram shows a dual mains system in which the upstream breakers are named Q. Correct settings of upstream breaker settings are mandatory. The system can also be configured as a single mains system.

T1

Q

T2

Q

Dual Mains Installation

Q3

Q5

Q1

Q6

 

Q2

Q4

22

Symmetra MW II 1200 kW 3 x 400/230 V Installation - 990-1979E-001

Page 26
Image 26
APC MW II manual Dual Mains Installation