Symmetra MW II 1200 kW 3 × 400/230 V Installation - 990-1979E-001

Service Entrance

Residual current protective device can not be used at this point.

Owing to parallel return path for the fault current

Residual Current Sense

N

With reference to IEC 60364-4-41 § 413.1.4.1

Earthing arrangements and protective conductors

-

Symmetra MWTTininstallation

 

 

 

 

 

See:

 

IEC 60364-4-41

§ 413.1.4

 

 

 

 

 

Switchgear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q3

 

 

 

 

( PDU )

 

 

 

 

 

 

 

 

 

 

 

Residual Current Sense

Residual current protective device

 

 

 

 

 

 

 

 

 

 

 

can be used.

Q5

 

 

 

 

 

External SSW-Bypass

 

 

Q6

 

 

 

Bypass - input

 

 

 

 

 

Bypass - output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

L1

 

 

 

 

 

 

L2

 

 

 

 

 

L2

 

 

 

 

 

 

L3

 

 

 

 

 

L3

 

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

PE

Q4

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

SymmetraMW

 

 

 

 

 

Q1

 

 

Mains - input

 

i

Delta

 

 

UPS - output

 

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

L1

 

 

i

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

 

i

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EarthingProtectiveCondu ctor

L3

 

 

 

u

 

L3

 

 

 

 

 

Common-mode filter

 

 

u

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

Main

 

 

 

 

 

 

 

 

 

 

 

 

inverter

 

 

 

 

 

 

 

 

N

 

 

 

 

 

N

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

PE

 

 

 

 

 

 

+

-

+

-

 

 

 

 

 

 

 

 

 

Battery 1

 

 

Battery 2

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

Suitable earth electrode: RA x

Ia

< 50V

breaker

 

 

 

 

 

 

 

 

 

With reference to IEC 60364-4-41

§ 413.1.4.2

box Q7

 

 

Q8

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

rack

 

 

 

 

 

 

 

 

 

 

 

 

Battery 1

 

Battery 2

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 