For discrimination purposes,
When the protective device is an overcurrent protective device, it must be either:
•a device with inverse time characteristics and Ia must be the current causing automatic operation within 5 seconds, or
•a device with an instantaneous tripping characteristic and Ia must be the minimum current causing instantaneous tripping
The following diagram shows a Symmetra® MW installed in a TT system:
• Earthing arrangements and protective conductors - Symmetra® MW in “TT installation”
IT Systems
Characteristics
In IT systems the installation is insulated from earth or connected to earth through a sufficiently high impedance. Exposed conductive parts are earthed individually, in groups, or collectively.
Reference to IEC 60364-4-41 413.1.5
In IT systems the installation must be insulated from earth or connected to earth through a sufficiently high impedance. This connection must be made either at the neutral point of the system or at an artificial neutral point. The latter may be connected directly to earth if the resulting
Exposed conductive parts must be earthed individually, in groups or collectively and the condition RA ⋅ Id ≤ 50V must be fulfilled.
In the condition:
RA | is the resistance of the earth electrode for exposed conductive parts |
Id | is the fault current of the first fault of negligible impedance between a phase conductor and an |
| exposed conductive part. The Id value takes the leakage currents and the total earthing impedance |
| of the electrical installation into account |
In systems where an IT system is used for continuity of supply, an insulation monitoring device must be provided to indicate the occurrence of a first fault from a live part to the exposed conductive parts or to the earth. It is recommended to eliminate a first fault as soon as possible.
26 | Symmetra MW II 1200 kW 3 × 400/230 V Installation - |