5.5 PROFIBUS-DP Bus Cables

PROFIBUS-DP Bus Cables

Siemens supply the following PROFIBUS-DP bus cables (see catalog ST 70):
PROFIBUS-DP bus cable 6XV1830-0AH10
PROFIBUS-DP cable for burying in ground 6XV1830-3AH10
PROFIBUS-DP trailing cable 6XV1830-3BH10
PROFIBUS-DP bus cable with PE sheath (for foodstuffsand
luxury food industry)
6XV1830-0BH10
PROFIBUS-DP bus cable festoons 6XV1830-3CH10

Characteristics of the PROFIBUS-DP Bus Cable

The PROFIBUS-DP bus cable is a twisted, shielded pair with the following
characteristics:
Characteristics Values
Impedance approx. 135 to 160 (f= 3 to 20 MHz)
Loop resistance 115 /km
Workingcapacitance 30 nF/km
Attenuation 0.9 dB/100m (f= 200 kHz)
Permissible core cross-section 0.3m m2to 0.5 mm2
Permissible cable diameter 8mm±0.5mm

Rules for Laying Cables

When you lay the PROFIBUS-DP bus cable, you should not:
Twist it ,
Stretch it, or
Compress it.
Furthermore, when installing the indoor bus cable, you must observe the following
basic conditions (dA= outer diameter of the cable):
Characteristics Boundary
Conditions
Bending radius for single bend 80 mm (10 x dA)
Bending radius for repeated bends 160 mm (20 x dA)
Permissible temperature range for installation -- 5 _Cto+50_C