Assembling and Installing Systems

120/230 VAC Supply

The following table shows which points you must observe when connecting the S7-400 to a 120/230 VAC supply.

With ...

... You Must Ensure ...

 

 

buildings

that suitable external lightning protection measures are

 

provided.

 

 

supply cables and signal

that suitable internal and external lightning protection

lines

measures are provided.

 

 

stationary equipment and

that a supply disconnector (switch) is installed in the

systems without all-pole

building.

disconnector

 

 

 

load power supplies and

that the set line voltage range corresponds to the local line

power supply modules

voltage.

 

 

all circuits of the S7-400

that fluctuations of line voltage from the rated value are

 

within permissible tolerances (see Technical Data of the

 

modules).

 

 

residual-current devices

that the RCD is suitable for the total discharge currents of

(RCDs)

the power supply module.

24 VDC Supply

The following table shows the points you must observe when connecting the S7-400 to a 24 VDC supply.

With ...

... You Must Ensure ...

 

 

buildings

that suitable external lightning protection measures are

 

provided.

 

 

24 VDC supply cables and

that suitable internal and external lightning protection

signal lines

measures are provided.

 

 

24 V supply

that the supply voltage produced is an isolated extra-low

 

voltage.

 

 

load power supplies

that only isolated load current power supplies are used.

 

 

Protection Against External Electrical Effects

The following table shows what you must observe for protection against external electrical effects.

With ...

... You Must Ensure ...

 

 

all plants and systems in

that the plant and all system sections are properly

which the S7-400 is

connected to protective ground to discharge

installed

electromagnetic interference.

 

 

connecting cables and

that all cables are correctly routed and connected.

signal lines

 

 

 

signal lines

that an open circuit in a signal line does not place the

 

equipment in an undefined state.

 

 

Automation System S7-400

Hardware and Installation

A-3

A5E00850741-01

 

Page 171
Image 171
Siemens S7-400 120/230 VAC Supply, VDC Supply, Protection Against External Electrical Effects, With You Must Ensure