Wiring the S7-400

Connecting the Load Voltage Ground

Many output modules require an additional load voltage to switch the actuators. Two different modes are possible for this load voltage:

Non-isolated operation

Floating operation

The following table shows how the load voltage ground is connected in the individual modes.

Table 4-3

Grounded connection load voltage

 

 

 

 

 

 

Mode

Connection of Load Voltage

 

 

Non-isolated operation

 

Grounded configuration

to the reference point of the rack; metallic connection

 

 

 

between frame element and chassis ground must be

 

 

 

fitted.

Ungrounded configuration

to the reference point of the rack; metallic connection

 

 

 

between frame element and chassis ground must be

 

 

 

fitted.

 

 

Floating operation

 

Grounded and ungrounded

Left open or to any point, but not to protective ground

 

configuration

or reference potential M of operating voltages

 

 

 

 

The following figure shows how the load voltage ground is connected for non-isolated operation.

Metallic connection, remove for ungrounded configuration

Ground terminal for load voltage

Figure 4-7 Grounded connection load voltage

4-14

Automation System S7-400

Hardware and Installation

 

A5E00850741-01

Page 74
Image 74
Siemens S7-400 installation manual Connecting the Load Voltage Ground, Mode Connection of Load Voltage