Wiring the S7-400

4-17

AutomationSystem S7-400 Hardwareand Installation
A5E00850741-01
4.11 Wiring Rules

Lines and Tools

For wiring the S7-400 modules, there are some rules for the cables and tools to

use.

Rulesfor ... PowerSupply ... Front Connectors
Crimp terminal Screw-type
terminal
Spring-type terminal
Conductor
cross-sections:
Outer diameter: 3to9mm
Flexible cond.
without wire end
ferrule
no 0.5to1.5mm
20.25to 2.5 m m20.08 to 2.5 mm2
Flexible cond. with
wire end ferrule
230 VAC:flexible
sheathed cable
3x1.5mm
2
24 VDC: flexible
sheathed cable
3x1.5mm
2or
individual wires
1.5m m2
no 0.25to 1.5 m m20.25 to 1.5 mm2
No. of conductors
per terminal
1 1 1*1*
Stripping length of
single conductors
7mm 5mm 8to 10 mm without
ferrule
10 mm with ferrule
8 to 10 mm without
ferrule
10 mm with ferrule
Wire end ferrules 230 VAC:with
insulating collar to
DIN 46228 E1,5-8
24 VDC: without
insulating collar to
DIN 46228, shape A,
short version
-with or without
insulating collar to
DIN 46228 Part 1
or 4, Shape A,
normal version
with or without
insulating collar to
DIN 46228 Part 1 or
4, Shape A, normal
version
Blade width and
shape of the screw
driver
3.5 mm (cylindrical
shape)
-3.5 mm (cylindrical
shape)
0.5m m x 3.5 mm
DIN 5264
Tighteningtorque:
for connecting
conductors
0.6to0.8Nm -0.6to0.8Nm -
*Youcan also connect a combination of two conductors of up to 1.0 mm each to a screw-type

or spring-loaded terminal. Youmust use special wire end ferrules for this purpose. Two types

and manufacturers of such ferrules are given below:

Phoenix TWIN Type no. 32 00 81 0, for 2 x 1 mm2

AMP Orderno. 966 144-4, for 2 x 1 mm2

Note

Youmust use shielded cables for the analog modules (see Section A.5).