Wiring the S7-400
4-26 AutomationSystem S7-400 Hardwareand Installation
A5E00850741-01
4.16 Wiring the Front Connector, Spring-TypeTerminals
Procedure
Towire the prepared front connector, follow the steps outlined below:
1. Areyou using wire end ferrules?
If so: Strip the conductors over 10 mm. Press-fit the wire end ferrules onto the
conductors.
If not: Strip the conductors over 8 to 10 mm.
2. Usea screwdriver (0.5 x 3.5 mm DIN 5264) to release the spring contact of the
first terminal. Start at the bottom of the front connector.
Youcan release the individual spring contacts at three points: from the front,
from the side or from the back (see Figure 4-15 ).
3. Pushthe first wire into the released spring contact and withdraw the
screwdriver.
4. Repeatsteps 3 and 4 for all other wires.
Releasing
a spring contact
from the front
Releasing
a spring contact
from the side
Releasing
a spring contact
from the back
Figure 4-15 Wiring a Front Connector with Spring-TypeTerminals