Installing the S7-400

Rules for Connection

When you connect a central rack to expansion racks, you must observe the following rules:

You can connect up to 21 ERs of the S7-400 to one CR.

The ERs are assigned numbers to identify them. The rack number must be set on the coding switch of the receive IM. Any rack number between 1 and 21 may be assigned. Numbers must not be duplicated.

You may insert up to six send IMs in one CR. However, only two send IMs with 5 V transfer are allowed in one CR.

Each chain connected to the interface of a send IM can comprise up to four ERs (without 5 V transfer) or one ER (with 5 V transfer).

The exchange of data via the communication bus is limited to 7 racks, meaning the CR and ER numbers 1 to 6.

The maximum (total) cable lengths specified for the type of connection must not be exceeded.

Type of Connection

Maximum (Total) Cable Length

 

 

Local connection with 5 V transfer via

1.5 m

IM 460-1 and IM 461-1

 

 

 

Local connection without 5 V transfer via

5 m

IM 460-0 and IM 461-0

 

 

 

Remote connection via IM 460-3 and

102.25 m

IM 461-3

 

 

 

Remote connection via IM 460-4 and

605 m

IM 461-4

 

 

 

Automation System S7-400

Hardware and Installation

2-5

A5E00850741-01

 

Page 21
Image 21
Siemens S7-400 installation manual Rules for Connection, Type of Connection Maximum Total Cable Length