Wiring the S7-400

4.10Interference-Free Configuration for Local and Remote Connections

Use only Approved Components

Note

If you use components which are not approved for setting up local and remote connections, interference rejection may be impaired.

Interference-Free Configuration for Local Connections

If you connect the CR and ER via suitable interface modules (send IM and receive IM), no particular shielding and grounding need be implemented. Ensure, however, that

All racks must have a low-impedance connection to each other

The racks in a grounded arrangement must have a star grounding configuration

The contact springs of the racks must be clean and may not be bent and will therefore ensure the discharge of interference currents.

Interference-Free Configuration for Remote Connections

If you connect the CR and ER via suitable interface modules (send IM and receive IM), normally no particular shielding and grounding need be implemented.

Special shielding and grounding may become necessary if you operate your system in an environment with an extremely high level of interference. In that case, observe the following points:

In the cabinet, connect the cable shields to the shield bus immediately after entry.

--Strip the outer cable insulation in the region of the shield bus without damaging the braided shield.

--Ensure that the braided shield has the greatest possible contact area on the shield bus, for example, with metal hose clamps surrounding the shield over a large area.

Connect the shield bus(es) over a large area to the frame or cabinet wall.

Connect the shield bus(es) to the chassis ground.

In a remote connection, ensure that the VDE regulations for laying the protective ground are not infringed.

Automation System S7-400

Hardware and Installation

4-15

A5E00850741-01

 

Page 75
Image 75
Siemens S7-400 installation manual Use only Approved Components, Interference-Free Configuration for Local Connections