Networking

Optical PROFIBUS-DP Network in Partyline Topology

The optical PROFIBUS-DP network with nodes that have an integrated fiber-optic cable interface has a partyline topology. The PROFIBUS nodes are interconnected in pairs by means of Duplex fiber-optic cables.

Up to 32 PROFIBUS nodes with a fiber-optic cable interface can be series-connected in an optical PROFIBUS-DP network. If a PROFIBUS node fails, as a result of the partyline topology none of the downstream DP slaves can be accessed by the DP master.

Programming

S7-400 with IM 467 FO

ET 200M with

Other field devices without

device/PC/OP

 

IM 153-2 FO

fiber-optic cable interface

PROFIBUS

 

 

 

cable

 

 

 

 

Distances between 2

 

 

OBT

nodes:

 

OBT

Plastic fiber-optic cable up

 

 

to 50 m

 

 

 

PCF fiber-optic cable up to

 

Other

 

300 m

 

 

 

nodes

 

Optical PROFIBUS-DP

 

 

 

 

Figure 5-13 Optical PROFIBUS-DP Network with Nodes that have an Integrated Fiber-Optic Cable Interface

Transmission Rate

The following transmission rates are possible when the optical PROFIBUS-DP network is operated with a partyline topology:

9.6 kbps

19.2 kbps

45.45 kbps

93.75 kbps

187.5 kbps

500 kbps

1.5 Mbps

12 Mbps

Automation System S7-400