Assembling and Installing Systems
A-18 AutomationSystem S7-400 Hardwareand Installation
A5E00850741-01
TableA-2 Cabling Inside Buildings, continued
Run ...and Cables for ...ConnectCables for ...
DC voltage
(>60 V and400 V),
unshielded
AC voltage
(>25 V and400 V),
unshielded
LAN signals, shielded
(SINEC L1, PROFIBUS DP)
Data signals, shielded
(programming devices, operator
panels, printers, counter inputs,
etc.)
Analog signals, shielded
DC voltage
(60 V), unshielded
Process signals
(25 V), shielded
AC voltage
(25 V), unshielded
Monitors (coaxial cable)
in separate bundles or cable
ducts (no minimum clearance
necessary)
DC voltage
(>60 V and 400 V), unshielded
AC voltage
(>25 V and 400 V), unshielded
in common bundles or cable
ducts
DC and AC voltages
(>400 V), unshielded
Inside cabinets:
in separate bundles or cable
ducts (no minimum clearance
necessary)
Outside cabinets:
on separate cable racks with a
clearance of atleast 10 cm
(3.93 in.)
DC and AC voltages
(>400 V), unshielded LAN signals, shielded
(SINEC L1, PROFIBUS DP)
Data signals, shielded
(programming devices, operator
panels, printers, counter inputs,
etc.)
Analog signals, shielded
DC voltage
(60 V), unshielded
Process signals
(25 V), shielded
AC voltage
(25 V), unshielded
Monitors (coaxial cable)
Inside cabinets:
in separate bundles or cable
ducts (no minimum clearance
necessary)
Outside cabinets:
on separate cable racks with a
clearance of atleast 10 cm
(3.93 in.)
DC voltage
(>60 V and 400 V), unshielded
AC voltage
(>25 V and 400 V), unshielded
DC and AC voltages
(>400 V), unshielded DC and AC voltages
(>400 V), unshielded in common bundles or cable
ducts
ETHERNET ETHERNET in common bundles or cable
ducts
Others in separate bundles or cable
ducts with a clearance of at least
50 cm (19.65 in.)