Assembling and Installing Systems

Low-Voltage Protection Elements for 2<--> 3

For the transition points between lightning protection zones 2 <--> 3 we recommend the surge protection components listed in the table below. This low-voltage protection must be used in S7-400 for CE compliance.

Table A-5 Surge Protection Components for Lightning Protection Zones 2 <--> 3

Ser.

 

Cables for ...

 

... .. equip transition point

Order No.

No.

 

 

 

 

 

2 <-> 3 with:

 

 

 

 

 

 

 

 

 

1

3-phase TN-C-System

3 pieces of

 

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

 

3-phase TN-S system

4 pieces of

 

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

 

3-phase TT system

3 pieces of

 

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

phase L1/L2/L3 to N

5SD7 030

 

 

 

 

 

 

 

 

 

 

 

1 piece of

 

DEHNgap C N-PE surge N to PE

900

131*

 

 

 

 

 

 

 

 

AC TN-S system

2 pieces of

 

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

 

AC TN-C system

1 piece of

 

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

 

AC TT system

1 piece of

 

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

phase L to N

5SD7 030

 

 

 

 

 

 

 

 

 

 

 

1 piece of

 

DEHNgap C N-PE surge N to PE

900

131*

 

 

 

 

 

 

 

2

24 VDC Power Supply

1 piece of

 

Blitzductor VT lightning conductor,

918

402*

 

 

 

 

 

type AD 24 V

 

 

 

 

 

 

 

 

 

 

3

Bus cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MPI RS 485

 

 

• Blitzductor CT surge arrester, type

919

506* and

 

 

 

 

 

 

MD/HF

919

570*

 

 

 

 

 

 

 

 

 

RS 232 (V.24)

1 piece of

 

• per conductor pair low-voltage

 

 

 

 

 

 

 

 

protection FDK 2 12 V

919

995*

 

 

 

 

 

 

 

 

4

Inputs of digital modules

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VDC

1 piece of

 

Low-voltage surge arrester,

919

993*

 

 

 

 

 

type FDK 2 60 V on insulated rail

 

 

 

 

 

 

 

 

 

 

 

 

 

2 pieces of

 

Surge arresters

 

 

 

 

 

 

 

 

 

 

 

 

120 VAC

 

 

DEHNrail 120 FML

901

101*

 

 

 

 

 

 

 

 

 

 

230 VAC

 

 

DEHNrail 230 FML

901

100*

 

 

 

 

 

 

 

5

Outputs of digital modu-

1 piece of

 

Low-voltage protection FDK 2 D 5 24

919

991*

 

les 24 VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Outputs of analog modu-

1 piece of

 

Low-voltage protection,

919

995*

 

les up to 12 V +/--

 

 

type FDK 2 12 V on insulated rail con-

 

 

 

 

 

 

 

nected with M-- of the power supply

 

 

 

 

 

 

 

for the modules.

 

 

 

 

 

 

 

 

 

* You can order these components directly at:

DEHN + SÖHNE

 

 

 

 

 

 

 

 

GmbH + Co. KG

 

 

 

 

 

 

 

 

Elektrotechnische Fabrik

 

 

Hans-Dehn-Str. 1

D-92318 Neumarkt

Automation System S7-400

Hardware and Installation

A-27

A5E00850741-01

 