Assembling and Installing Systems

Low-Voltage Protection Elements for 1 <--> 2

For the transition points between lightning protection zones 1 <--> 2 we recommend the surge protection components listed in table A-4

Table A-4

Low-Voltage Protection Components for Lightning Protection Zones 1 <--> 2

 

 

 

 

 

 

 

Ser.

 

Cables for ...

... equip transition point 1 <-> 2 with:

Order No.

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

1

3-phase TN-C system

3 pieces of

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

3-phase TN-S system

4 pieces of

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

3-phase TT system

3 pieces of

DEHNguard 275 surge arresters

900

600*

 

 

 

 

phase L1/L2/L3 to N

5SD7 030

 

 

 

 

 

 

 

 

 

 

1 piece of

DEHNgap C N-PE surge N to PE

900

131*

 

 

 

 

 

 

 

AC TN-S system

2 pieces of

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

AC TN-C system

1 piece of

DEHNguard 275 surge arresters

900

600*

 

 

 

 

 

 

5SD7 030

 

 

 

 

 

 

 

AC TT system

1 piece of

DEHNguard 275 surge arresters

900

600*

 

 

 

 

phase L to N

5SD7 030

 

 

 

 

 

 

 

 

 

 

1 piece of

DEHNgap C, N-PE surge

900

131*

 

 

 

 

arrester, N to PE

 

 

 

 

 

 

 

 

2

24 VDC Power Supply

1 piece of

Blitzductor VT lightning

918

402*

 

 

 

 

conductor, type AD 24 V

 

 

 

 

 

 

 

 

 

3

Bus cable

 

 

 

 

 

 

 

 

 

 

 

 

 

MPI RS 485

 

• Blitzductor CT surge arrester,

919

506* and

 

 

 

 

 

type MD/HF

919

570*

 

 

 

 

 

 

 

 

 

RS 232 (V.24)

1 piece of

per conductor pair

919

506* and

 

 

 

 

 

surge arrester Blitzductor CT

 

 

 

 

 

type ME 15 V

919

522*

 

 

 

 

 

 

4

Inputs of digital modules 24

1 piece of

Low-voltage surge arrester,

919

993*

 

VDC

 

type FDK 2 60 V

 

 

 

 

 

 

 

 

5

Outputs of digital modules 24

1 piece of

Low-voltage surge arrester

919

991*

 

VDC

 

FDK 2D5 24

 

 

 

 

 

 

 

 

6

Inputs/outputs of digital

2 pieces of

Surge arresters

 

 

 

modules

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 VAC

 

DEHNguard 150

900

603*

 

 

 

 

 

 

 

 

 

230 VAC

 

DEHNguard 275

900

600*

 

 

 

 

 

 

7

Inputs of analog modules up

1 piece of

Surge arrester

919

506* and

 

to 12 V +/--

 

Blitzductor CT type MD 12 V

919

541*

 

 

 

 

 

 

* You can order these components directly at:

DEHN + SÖHNE

 

 

 

 

 

 

GmbH + Co. KG

 

 

 

 

 

 

Elektrotechnische Fabrik

 

 

Hans-Dehn-Str. 1

D-92318 Neumarkt

A-26

Automation System S7-400

Hardware and Installation

 

A5E00850741-01

Page 194
Image 194