provide smooth, reliable actuation at all times. Modulating valves shall be complete with positioners by the same manufacturer. Where indicated, position switches by the same manufacturer shall be provided.

2.08AUXILIARY DEVICES - PNEUMATIC A. Room Thermostats:

1.All room thermostats shall be high-capacity, relay type, with pneumatic feed-back,

adjustable sensitivity (1 to 4 psi°F minimum), and an output test port. Provide indicating set point, locking covers (Allen-head screws, or other means), as noted on drawings.

2.Provide single temperature thermostats for heating-only or cooling-only applications, direct-or reverse-acting with range as required.

3.Deadband thermostats are not acceptable. For heating/cooling applications, utilize non-overlapping spring ranges on the heating/cooling devices to achieve a deadband.

4.Provide recessed, aspirating thermostats or conventional thermostats with locking enclosures/gaurds for all thermostats located in public areas, such as lobbies, corridors, auditoriums, gyms, pools, theaters, stores, warehouses, garages, classrooms, etc.

B.Pressure-Electric (PE) Switches:

1.Provide one or two-stage switch action SPDT, DPST, or DPDT, as required by application. Electrically rated for pilot duty service (125 VA minimum), and/or for motor control.

2.Shall be open type (panel-mounted) or enclosed type for remote installation. Enclosed type shall be NEMA 1, unless otherwise specified.

3.Furnish permanent indicating gauge on each pneumatic signal line to PE switches.

C.Electro-Pneumatic (EP) Solenoid Air Valves:

1.Shall be snap-acting, three-way air valve with three ports (common, N.O. and N.C.), UL-listed.

2.Provide diecast or plastic body with stainless steel trim. Minimum safe pressure shall be 30 psig at 130F ambient and 130F control air temperatures.

3.Coil voltage as required up to 120VAC

4.Provide open type (panel-mounted) or enclosed type for remote installation. Enclosed in type NEMA 1 unless otherwise specified.

D.Current-Pneumatic (I/P) and Pneumatic-Current (P/I) Transducers:

1.Shall accept industry standard inputs and provide standardized outputs.

JANUARY 2008

UCCS STANDARDS

15950-22

Page 22