2.02AIR TUBING AND CONTROL WIRING
A.Air tubing shall be either copper (ACR) in exposed areas, or Type FR polyethylene (within conduit). Soft copper is acceptable in concealed areas.
B.Cables shall be shielded when so recommended by manufacturer. Conductor size shall be in accordance with manufacturer's recommendations subject to specified minimum size. See Part 3 for allowable types.
C.All insulated wire to be copper conductors, UL labeled for 90C minimum service.
D.Raceway for both wiring and pneumatic tubing shall be per Division 16.
E.The Contractor shall provide and install:
1.TVSS surge protectors for incoming 120 VAC power to all controllers. Surge protectors furnished shall be UL 1449 listed.
2.Transient voltage protection for all twisted pair and coaxial data communication lines between controllers. Provide all required repeaters to assure signal integrity.
2.03CONTROL VALVES
A.Shall be
B.Closeoff (differential) Pressure Rating: Valve actuator and trim shall be furnished to provide the following minimum closeoff pressure ratings:
1.Water Valves:
a.
b.
2.Steam Valves: 150% of operating (inlet) pressure.
C.Water Valves: [Note to Consultant: The consultant shall provide a schedule for the
Controls Contractor listing the available pressure drop to be used for valve sizing for each control valve in the project, unless it is a
1.Body and trim style and materials shall be per manufacturer's recommendations for design conditions and service shown, with equal percentage ports for modulating service, except where stated otherwise.
JANUARY 2008 | UCCS STANDARDS |