1.Not allowed.
D.Standard Nomenclature for Valve and Damper Position Description:
1.Set up the conversion table for each valve or damper control output so that 100% OPEN = open and 0% OPEN = closed.
2.For
3.For face and bypass dampers, 100% OPEN = face damper fully open and bypass damper closed. This would apply to both a face and bypass damper for a heating coil, which is normally open to the coil; and to a face and bypass damper for a evaporative cooling pad, which is normally closed to the pad.
E.Setup of Setpoints
1.The Setpoint Box in the CX and Cyberstation software shall be checked for all numerical points to be used as setpoints or any type of constant value point.
F.Setup of Inputs
1.THRESHOLDS:. The threshold shall be
Temperature (Space, OAT, MAT, DAT, RAT, etc.) .1F
Space Static Pressure 0.01”W.C.
Duct Static Pressure 0.2W.C.
Relative Humidity (Space, OAT, MAT, DAT, RAT, etc.) 1%
G.Provide
H. Protect all points where pneumatic tubing or sensing elements come in contact with metallic surfaces by enclosing the tubing or sensor with a section of
I.Seal all penetrations into ductwork or
J.Mount all control valves so that the stem is vertical. Prior approval is required from the UCCS HVAC Shop for all installations where this cannot be achieved.
K
JANUARY 2008 | UCCS STANDARDS |
|