2.Sizing Criteria:

a.Two-position service: Line size.

b.Two-way modulating service: Pressure drop across the valve in a wide-open position, with full flow through the valve, shall be equal to 50% of the available pressure differential between the mains, with a minimum of 4 psi.

c.Three-way Modulating Service: Pressure drop across the valve in a wide-open position, with full flow through the valve, shall be equal to twice the pressure drop through the heat exchanger (load), with a 3 psi minimum..

3.Construction:

a.Valves 1/2" through 2" shall be bronze body or cast brass ANSI Class 250, spring loaded, Teflon or ring packing, and stainless steel stems. Two-way valves to have replaceable composition disc.

b.2-1/2" valves and larger shall be cast iron ANSI Class 125 with guided plug, stainless steel stems and Teflon or ring packing.

4.Water valves shall fail as specified in the Control Sequences section .

5.Evaporative Cooler Drain and Fill Valves:

a. Valve normal position shall be as shown on the drawings.

6.For systems with glycol solutions, provide documentation that the valve components

in contact with the fluid are compatible with it.

2.04CONTROL DAMPERS [NOTE TO CONSULTANT: INCLUDE WORDING IN THE

AIR-HANDLING UNIT SECTION OF THE SPECIFICATION STATING THAT DAMPERS PROVIDED WITH EQUIPMENT SHALL MEET THE

REQUIREMENTS LISTED BELOW]

A.Motorized dampers, unless specified elsewhere, shall be as follows:

1.Damper frames shall be 13 gauge galvanized steel channel or 1/8" extruded aluminum with reinforced corner bracing.

2.Damper blades shall not exceed 8" in width or 48" in length. Blades are to be suitable for medium-velocity performance (2,000 fpm). Blades shall be not less than 16

gauge.

3. Damper shaft bearings shall be as recommended by manufacturer for application.

4. All blade edges and top and bottom of the frame shall be provided with replaceable

butyl rubber or neoprene seals. Side seals shall be spring-loaded stainless steel. The blade seals shall provide for a maximum leakage rate of 10 CFM per square foot at 4" w.c. differential pressure. Pressure drop shall not exceed 0.04" w.c. for airfoil blades, or 0.10"w.c. for regular blades, at a wide open face velocity of 1,500 FPM.