a.Combination heating/cooling thermostats shall have independent adjustments for heating and cooling setpoints and shall not allow setpoint
b.Provide individual heat or cooling anticipator for each control stage. Anticipator shall be matched to connected load, or shall be adjustable.
c.
4.Provide locking enclosures/guards for all thermostats located in public areas such as lobbies, corridors, gyms, cafeterias, classrooms, auditoriums, pools, theaters, stores, warehouses, garages, etc.
B.Room Humidistat:
1.All
2.Provide metal guards with security screws for all humidstats located in public areas such as lobbies, corridors, gyms, cafeterias, classrooms, auditoriums, pools, theaters, stores, warehouses, garages, etc.
C.Duct, Immersion, and Outdoor Thermostats:
1.Provide single or multistage type with contact arrangement and rating suitable for application. Line voltage units shall be
2.Sensing element shall be
a.Remote bulb type shall have sufficient capillary lengths to allow mounting of thermostat at convenient location for adjustment.
b.Provide separable wells for immersion applications.
c.Provide sun shields for outdoor sensing bulbs.
d.Provide ambient temperature compensation where thermostat body is subjected to outdoor ambient temperature variations.
3.Individual stage differential
D.Duct Humidistats:
1.Shall be line or
JANUARY 2008 | UCCS STANDARDS |
|