Alcove Installation Requirements

Whenever the stove is placed in a location where the ceiling height is less than 7' tall, it is considered an alcove installation. Because of the reduced height, the special installation requirements listed below must be met.

Chimney connector and chimney must be one of the following types:

• DURAVENT model DVL with DURATEC chimney

• GSW Double Wall Chimney Connector with Super Chimney Twenty-One

• DURAVENT model DVL with DURA-PLUS chimney

• SELKIRK METALBESTOS model DS connector with model SSII chimney

AMERI-TEC model DCC with model HS chimney

• I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector

• SECURITY model DL with SECURITY model ASHT or S2100 chimney

• Standard Masonry Chimney with any one of the above listed connectors

METAL-FAB model DW with TG chimney

 

 

 

 

Pendleton - 45°

Pendleton - 90°

Minimum

Clearance

Combustible

Non-Combustible

Combustible

Non-Combustible

(See

the

illustration below)

Alcove

Alcove

Alcove

Alcove

 

 

 

 

A

Sidewall to stove

11"

6"

11"

6"

B

Backwall to stove

13"

5"

8 1/2"

2"

D

Connector to sidewall

19 1/2"

14 1/2

19 1/2"

14 1/2"

E

Connector to backwall

9"*

2 1/2"*

8 3/4"

2 1/4"

G

Maximum depth of alcove

48"

48"

48"

48"

H

Minimum width of alcove

45 3/4"

35 3/4"

45 3/4"

35 3/4"

J

Minimum height of alcove

84"

6" above stove top

84"

6" above stove top

Alcoves are classified as combustible or non-combustible. Non-combustible alcoves must have walls and a ceiling that are 3 1/2" thick of a non-combustible material (brick, stone, or concrete). This non-combustible material must be spaced and ventilated at least 1" off of all combustible materials (walls, ceiling, etc.) to allow air to move around the non-combustible walls and ceiling. All other alcoves are considered combustible. The clearances below must be met:

Non-combustible alcove construction (on walls and ceiling) - see the explanation above.

Ventilated

air space

3 1/2" thick non- combustible material

1" Min.

Combustible

materials

Non-combustible reinforcer

d

e

a

b

j

h

g