Avalon Stoves 790 Insert Size Requirements see Illustration below, Insert Placement Requirements

Models: 790 745

1 44
Download 44 pages 20.04 Kb
Page 18
Image 18
18 Insert Installation (for qualified installers only)

18 Insert Installation (for qualified installers only)

Insert Size Requirements (see Illustration below)

 

Combustible

Mantel

 

 

 

 

j

 

 

 

 

 

 

Non-

 

 

h

i

Combustible

Facing

 

 

 

 

 

a

b

 

 

 

 

 

 

 

 

 

 

 

 

d

 

Non-

c

 

e

 

 

 

 

 

 

 

 

 

 

Combustible

Hearth

 

g

 

 

 

 

 

 

f

Insert Placement Requirements

M i n i m u m

Masonry

Z.C. (Metal)

Fireplace Size

Fireplace

Fireplace

a

Height (front)

21 1/2"

21 1/2"

b

Height (rear)

21 1/2"

21 1/2"

c

Width (front)

23 3/4"

25 3/4"

d

Width (rear)

23 3/4"

25 3/4"

e

Depth

11 3/8"

12 3/8"

f

Hearth Depth*

20 3/4"

20 3/4"

g

Hearth Width

39 3/4"

39 3/4"

h

Facing Width

41 3/4"

47 3/4"

i

Facing Height

39"

31"

j

Mantel Height

41"

43"

*This is the distance the insert protrudes from the fireplace opening plus the required 16" of hearth extension.

The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the insert

Insert and hearth must be installed on a level, secure floor

The minimum clearances, facing, and hearth requirements in the illustration below must be met (follow the clearances for the type of fireplace being used - either masonry or zero-clearance).

 

Combustible

Mantel

 

 

 

 

 

 

 

Side

n

Combustible

Top

 

Wall

 

 

 

Facing

 

 

 

 

 

 

 

 

 

 

 

m

 

 

 

k

l

 

 

 

 

 

 

 

 

 

 

p

 

 

 

 

 

Non-

 

 

 

 

q

HearthCombustible

 

o

 

x

 

 

 

 

 

Facing

Minimum Clearances

Masonry

ZC (Metal)

 

 

Fireplace

Fireplace

k

Sidewall to Insert

10"

30"

l

Side Facing

9"

12"

m

Top Facing

20"

12"

 

w. Mantel Shield

14 1/2"

n/a

n

Mantel to Insert

22"

24"

 

w. Mantel Shield

16 1/2"

n/a

o

Hearth (Front)*

16"

16"

p

Hearth (Side)

8"

8"

q

Front of Insert

36"

36"

x

Extension onto Hearth

4 3/4"

4 3/4"

*Does not include the distance the insert extends onto the hearth (dimension "x").

Hearth Requirements

Must extend 16" in front of the insert and 8" on both sides

Must be non-combustible 1/4" thick insulating board with a thermal conductivity of K = 0.72

Travis Industries

93508133

4 020509

Page 18
Image 18
Avalon Stoves 790, 745 Insert Size Requirements see Illustration below, Insert Placement Requirements, Hearth Requirements