Avalon Stoves 745, 790 owner manual Stove Placement Requirements, Clearances

Models: 790 745

1 44
Download 44 pages 20.04 Kb
Page 9
Image 9
Stove Placement Requirements

Stove Installation (for qualified installers only)

9

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or other means approved by local building or fire officials.

Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the stove

If the stove is placed in a location where the ceiling height is less than 7', it must follow the requirements in the section "Alcove Installation Requirements"

Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):

Clearances

Corner Installations

Straight Installations

d

e

f

a

b

c

NOTE:

Measure clearances to the stove top.

 

 

 

Pendleton - 45°

Pendleton - 90°

Minimum

Clearance

Singlewall

Reduced

Singlewall

Reduced

(See

the

illustration above)

Connector

Clearance*

Connector

Clearance*

A

Sidewall to stove

10"

11"

10"

11"

B

Backwall to stove

19 1/2"

13"

16 1/2"

8 1/2"

C

Cornerwall to stove

9 1/2"

7 1/2"

9 1/2"

7 1/2"

D

Connector to sidewall

19"

19 1/2"

19"

19 1/2"

E

Connector to backwall

17 1/2"**

9"**

17 1/4"

8 3/4"

F

Connector to cornerwall

16"**

11"**

17 1/2"

15"

*

Reduced clearance installations require one of

the chimneys and connectors listed below:

 

• DURAVENT model DVL with DURATEC chimney

• GSW Double Wall Chimney Connector with Super Chimney Twenty-One

 

• DURAVENT model DVL with DURA-PLUS chimney

• SELKIRK METALBESTOS model DS connector with model SSII chimney

 

AMERI-TEC model DCC with model HS chimney

• I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector

 

• SECURITY model DL with SECURITY model ASHT or S2100 chimney

• Standard Masonry Chimney with any one of the above listed connectors

METAL-FAB model DW with TG chimney

**These are minimum clearances, not installation dimensions. Connector position will vary depending upon brand. First establish the stove clearances, install the 45° connector to the stove, then determine the position of the connector.

NOTE : Standard residential installations with reduced clearance connector may use the clearance determined by the manufacturer of the connector for the connector to wall clearance or the clearance listed in this manual. Offsets must be used to maintain the stove to wall clearance.

NOTE : Reduced clearance connectors may not connect to the flue collar – order an appliance adapter for the connector being used.

Travis Industries

93508133

4 020509

Page 9
Image 9
Avalon Stoves 745, 790 Stove Placement Requirements, Clearances, Stove Installation for qualified installers only