28EVR1500 Installer/User Guide
Figure 3.10: Analog Inputs Window
3.Click the Enabled checkbox to enable the analog sensor input.
NOTE: An enabled analog input will display in the Main tab window and will be available for use
in the following operations: Calculations, SNMP actions, Output actions, Thresholds, Rules, Timed Rules and Reports.
4.If desired, edit the name of the analog input by typing a new name in the Unique name field. The name cannot contain any spaces. The only special character allowed is the underscore (_).
5.Type the minimum voltage input range (for example, Ø, 1 or 2 volts) in the Raw minimum value field. This range is the minimum DC voltage range output from the sensor.
6.Type the maximum voltage input range (for example, 5 or 10 volts) in the Raw maximum value field. This value is the maximum DC voltage range output from the sensor.
7.Type the analog input’s converted minimum value (for example,
8.Type the analog input’s converted maximum value (for example, 85 degrees F) in the Converted maximum value field.
NOTE: Values for steps 5 to 8 are provided with the analog sensor documentation.