Chapter 4: Advanced Operations | 55 |
|
|
To delete a threshold:
1.After launching the web GUI, click Application - Thresholds. The Thresholds window displays a list of thresholds.
2.Click the row containing the threshold you wish to delete.
3.Click the Delete button to delete the selected threshold.
4.Click the Save button to save the change.
Configuring Rules
The Rules feature enables you to configure periodic
The rule shown in Figure 4.2 is used to control a fan connected to a digital output. The value in the Value to test field (Temp1) is a calculation that will equal 1 if an analog input exceeds 85 degrees F. If the analog input falls below 85 degrees F, the Temp1 calculation will equal Ø. This rule scans the Fan_ Temp calculation every 60 seconds and either turns the output connected to the fan on (Temp1 = 1) or off (Temp1 = Ø). An output action is used to toggle the digital output.
Figure 4.2: Rules Window