Typical AGM300 Relay 1 and Relay 2 Wiring
LEAK SPILL EVACUATE FAULT
Horn
Line | Neutral |
Aux. Power
Line | Neutral |
|
|
Main AC Input
Jumper the ‘Neutral’ of the auxiliary power connector to the ‘Common’ on the relay block.
Connect one end of strobe or horn to the ‘NO’ of whichever level of alarm is appropriate for application. The other end of strobe or horn is connected to the ‘Line’ of the auxiliary power connector (5 A max.).