CRITICAL FAULTS

NO FLOW ON ZONE – Go to the System Screen (Page 47) and press the ZONES key. The Zone Screen (Page 44) will display a “NO FLOW” message in each individual zone affected. Check for a blockage in the air sample line or at the line end filter. Once the blockage has been cleared, the AGM300 will return to normal operation after the zone has been sampled. NOTE: This can take some several minutes since it is dependent upon how many zones there are and their lengths. The AGM300 will clear the fault the next time it polls the effected zone and the ADM800 will return to normal operation the next time that it polls the AGM300.

NO FLOW ON PURGE – Check the purge line for a blockage. Verify that the length of the purge line and exhaust line do not exceed 300 feet in length.

NO FLOW DETECTED – Check for proper pump operation. Check the water trap – drain if necessary.

CLIPPING FAULT – The detector voltage may be out of tolerance. Check the Diagnostic Screen (Page 59) for the DET voltage, AVE voltage and ZERO voltage. Call the factory with this information for further instructions.

REZERO VOLT TOL – The detector output voltage is out of tolerance. Check the Diagnostic Screen as in item 4 and contact the factory for assistance.

TRIGGER FAULT – No trigger from IR source pulser. Contact factory with all information from the Diagnostic Screen for further instructions.

NON CRITICAL FAULTS

BOX TEMP FAULT – Enclosure’s internal temperature is outside normal range (or IR sensor has failed). Check the installation to verify that the monitor is not being subjected to extreme temperatures. Verify that the ventilation holes are not obstructed. Check the Diagnostic Screen for the ZERO temperature, BNCH temperature and BOX temperature. Call the factory with this information for further instructions.

BENCH TEMP FAULT – Optical bench is outside of normal operating range (or sensor has failed). Check the installation to verify that the monitor is not being subjected to extreme temperatures. Check the Diagnostic Screen for the ZERO temperature, BNCH temperature and BOX temperature. Call the factory with this information for further instructions.

PRESSURE SENSOR – Manifold pressure is outside normal operating range (or sensor has failed). Check the Diagnostic Screen and record ALL data. Call the factory with this information for further instructions.

LOOP FAULT – This would only be displayed if the dual 4–20 mA option was installed and one or both current loops are open. Check the wiring to load/monitoring circuit on both 4–20 mA loops.

CONFIG FAULT – There is an error in AGM Setup Screen #2 – Number Zones Installed field, or in ADM Setup Screen #1 – Number of AGMS on Network field. Check that the number of zones installed for each AGM unit and the number of AGM units on the network are properly programmed. Check to ensure that the manifold solenoid cable connector in each AGM unit is securely fastened to its terminal connector. Check for an illegal parameter. If necessary, reset to the factory default settings.

Reset to Factory Default Settings

IMPORTANT: Performing this function wipes out all program parameters, alarms, faults, trends and log files.

Resetting the AGM300 – Press and hold down the Factory Default switch inside the AGM300 (Page 7); cycle the AC power OFF and then ON; listen for five beeps; and then release the switch. Reprogram the AGM300 per Section AGM300 – Setup Programming on Page 37.

Resetting the ADM800 – Occasionally it will be necessary to rest the ADM800 to factory default settings. From the System Screen (Page 31), press and hold the key adjacent to the ALARMS function; cycle AC power OFF and then ON; listen for five beeps; and then release the key.

Instruction 3015-4275

55

Page 63
Image 63
Bacharach AGM300, ADM800 manual Reset to Factory Default Settings, Critical Faults

AGM300, ADM800 specifications

The Bacharach ADM 800 and AGM 300 are advanced analyzers designed for efficient monitoring and detection of gases in various applications. Known for their reliability and accuracy, these instruments cater to commercial and industrial sectors, ensuring safety and compliance with environmental regulations.

The Bacharach ADM 800 is a portable gas detection device renowned for its ability to detect multiple refrigerants. With a user-friendly interface, it features a high-resolution display that provides real-time data on refrigerant concentrations, allowing technicians to quickly identify leaks during maintenance operations. One of its standout technologies is a highly sensitive thermal conductivity sensor, which enables the ADM 800 to differentiate between various hydrocarbon refrigerants with precision.

Equipped with data logging capabilities, the ADM 800 can store and retrieve measurement data, making it an invaluable tool for tracking refrigerant trends over time. The device supports USB connectivity for easy transfer of data to computers, facilitating detailed reporting and analysis. Its robust design incorporates a protective casing that ensures durability in challenging work environments, making it ideal for both field use and stationary applications.

On the other hand, the Bacharach AGM 300 is specifically crafted for continuous gas monitoring in HVAC systems. This stationary device excels in measuring concentrations of gases such as CO, CO2, and various refrigerants, ensuring optimal performance and compliance. The AGM 300 uses advanced electrochemical sensors for precise gas measurements, providing real-time feedback and alerting users to any hazardous conditions.

One of the notable features of the AGM 300 is its ability to integrate seamlessly with building management systems, enabling centralized control and monitoring of gas levels across multiple locations. This connectivity enhances the safety of industrial and commercial spaces by allowing for automated responses to detected gas levels, which can significantly mitigate risks associated with gas leaks.

Both models emphasize user-centric design, with intuitive interfaces and clear displays, making them accessible even to those with minimal training. Additionally, their low maintenance requirements and long sensor life contribute to reduced operational costs.

In conclusion, the Bacharach ADM 800 and AGM 300 are exemplary solutions for gas detection and monitoring. Their advanced technologies, robust features, and user-friendly designs make them indispensable for ensuring safety and regulatory compliance in various environments.