Tubing Considerations
Use ¼" outside diameter (0.040" wall) flex tubing is used for all air lines (P/N
IMPORTANT: Due to the reactive nature of ammonia gas, it is important to use materials that will not absorb ammonia gas as it passes though the sampling system. The use of unauthorized tubing or any other materials in the gas sampling stream may lead to erroneously low readings.
To connect the air lines to the monitor simply push the tubing firmly onto the connector. All tubing bends should have a radius of no less than 5" to assure proper airflow. If kinks or obstructions occur in any of the air lines the instrument may not function properly.
Connecting Purge Line
A purge line is required to draw fresh air into the instrument and should not exceed 300 feet in length. It is advisable to terminate the line outdoors, provided the input is not exposed to rain, snow, ice, exhaust fumes, or other airborne contaminates. If an outdoor installation is impractical, the line should be run to an area inside the facility that you are certain is not contaminated with ambient ammonia gas. A
Connecting Exhaust Line
An exhaust line is required to vent gas samples away from the instrument and should not exceed 300 feet in length. The exhaust line should terminate in a location that is completely isolated from the purge line termination point and other areas of the facility that will be monitored. Ideally this line should terminate outdoors in a location that is not exposed to the elements. This line does not require a
Connecting Sample Intake Lines
The AGM300 is designed to accommodate up to 16 separate sample intake lines. The standard configuration of the unit includes one manifold of 4 intake connectors and 1 purge connector. Additional manifolds can be easily installed to increase monitoring capacity (field installation kit part P/N
Sample intake lines can be up to 500 feet in length. All line terminations should be positioned to reduce the possibility of mists, aerosols, oil, water, dust, or other contaminates being drawn into the instrument. A
IMPORTANT: DO NOT plug any of the zones. Plugging a zone will give the monitor a false indication during start up.
Please refer to the earlier Section Suggested Location of Sampling Points to learn more about where to place the ends of the sample intake lines.
Water Trap
A water trap has been installed as a standard feature. The water trap prevents condensation or moisture from entering the infrared device and causing serious damage. To empty the water trap, loosen the wing nut and allow water to drain – be sure to retighten the wing nut.
CAUTION - The introduction of contaminants through the air intake lines can result in serious and permanent damage to the monitor.