8 ACTUATOR CONTROL

MUZ-FD09NA

MUZ-FD12NA

8-1. OUTDOOR FAN MOTOR CONTROL

The fan motor turns ON/OFF, interlocking with the compressor.

[ON] The fan motor turns ON 5 seconds before the compressor starts up.

[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

5 seconds

15 seconds

ON

Compressor

OFF

ON

Outdoor fan motor

OFF

8-2. R.V. COIL CONTROL

Heating . . . . . . . . . . . . . . . . . ON

Cooling . . . . . . . . . . . . . . . . . OFF

Dry . . . . . . . . . . . . . . . . . . . . OFF

NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

<COOL><HEAT>

 

 

5 seconds

 

 

5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

Compressor OFF

 

 

 

 

 

 

 

R.V.coil

ON

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor fan ON

 

 

 

 

 

 

 

motor

OFF

 

 

 

 

 

 

 

8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

 

 

 

 

 

 

Sensor

 

Purpose

 

 

Actuator

 

 

 

Compressor

LEV

Outdoor

R.V. coil

Indoor fan

 

 

 

 

 

fan motor

motor

 

 

 

 

 

 

 

 

Discharge temperature thermistor

 

Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor coil temperature thermistor

 

Cooling : Coil frost prevention

 

 

 

 

 

 

 

Heating : High pressure protection

 

 

 

 

 

 

 

 

 

 

 

 

Defrost thermistor

 

Cooling : High pressure protection

 

 

 

 

 

 

Heating : Defrosting

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin temperature thermistor

 

Protection

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor heat exchanger temperature thermistor

 

High pressure protection

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature thermistor

 

Low ambient temperature operation

 

 

 