SPECIFICATION

3

 

 

SPECIFICATION

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit model

 

 

 

 

 

MUZ-FD09NA

 

MUZ-FD12NA

 

 

 

 

 

 

 

 

 

Capacity

 

Cooling

1

Btu/h

 

9,000 (2,800~9,000)

 

12,000 (2,800~12,000)

Rated (Minimum~Maximum)

Heating 47

1

Btu/h

 

10,900 (3,000~18,000)

 

13,600 (3,000~21,000)

Capacity Rated

Heating 17

2

Btu/h

 

7,700

 

8,300

Power consumption

Cooling

1

W

 

650 (160~650)

 

960 (160~960)

Rated (Minimum~Maximum)

Heating 47

1

W

 

750 (150~2,400)

 

980 (150~2,400)

Power consumption Rated

Heating 17

2

W

 

1,730

 

1,780

EER 1 [SEER] 3

Cooling

 

 

 

 

13.8 [23.0]

 

12.5 [22.0]

HSPF IV(V)

4

Heating

 

 

 

 

10.55 (7.4)

 

10.55 (7.4)

COP

 

Heating

 

1

 

 

4.30

 

4.10

External nish

 

 

 

 

 

Munsell 3Y 7.8/1.1

Power supply

V , phase , Hz

 

 

208/230 , 1 , 60

Max. fuse size (time delay)

 

 

A

 

 

15

Min. circuit ampacity

 

 

 

A

 

 

12

Fan motor

 

 

 

 

F.L.A

 

 

0.56

Compressor

Model

 

 

 

 

 

SNB130FQAH

 

 

 

R.L.A

 

 

8.6

 

 

 

 

 

 

 

L.R.A

 

 

10.8

Refrigerant control

 

 

 

 

 

Liner expansion valve

Sound level

1

Cooling

 

 

dB(A)

 

48

 

48

Heating

 

 

dB(A)

 

49

 

49

 

 

 

 

 

 

 

 

Defrost method

 

 

 

 

 

 

Reverse

cycle

Dimensions

 

W

 

 

in.

 

 

31-1/2

 

D

 

 

in.

 

 

11-1/4

 

 

 

 

H

 

 

in.

 

 

21-5/8

Weight

 

 

 

 

Ib.

 

 

80

Remote controller

 

 

 

 

 

 

Wireless type

Control voltage (by built-in transformer)

VDC

 

 

12 - 24

Refrigerant piping

 

 

 

 

 

 

Not supplied

Refrigerant pipe size

Liquid

 

 

in.

 

 

1/4 (0.0315)

(Min. wall thickness)

Gas

 

 

in.

 

 

3/8 (0.0315)

Connection method

Indoor

 

 

 

 

 

Flared

Outdoor

 

 

 

 

 

Flared

 

 

 

 

 

 

 

 

 

Between the indoor &

Height differ-

ft.

 

 

40

ence

 

 

 

 

outdoor units

 

 

 

 

 

 

 

 

Piping length

ft.

 

 

65

 

 

 

 

 

 

Refrigerant charge (R410A)

 

 

 

 

 

2 lb. 9 oz.

Refrigeration oil (Model)

 

 

 

 

 

NE022

NOTE : Test conditions are based on ARI 210/240.

1 : Rating conditions (Cooling) — Indoor : 80 FDB, 67 FWB, Outdoor : 95 FDB, (75 FWB)Rated frequency (Heating) — Indoor : 70 FDB, 60 FWB, Outdoor : 47 FDB, 43 FWB Rated frequency

MUZ-FD09NA2 :(Heating) — Indoor : 70 FDB, 60 FWB, Outdoor : 17 FDB, 15 FWBMaximum frequency