Installation GAS PIPING

Gas Connection

GAS PIPING

A properly sized gas supply system is essential for maximum oven performance. Piping should be sized to provide a supply of gas sufficient to meet the maximum demand of all appliances on the line without loss of pressure at the equipment.

Example:

NOTE: BTU values in the following example are for natural gas.

You purchase a Model 911 deck oven to add to your existing cook line.

1. Add the BTU rating of your current appliances.

Pitco Fryer

120,000

BTU

6 Burner Range

60,000

BTU

Convection Oven

50,000

BTU

Total

230,000

BTU

2.Add the BTU rating of the new oven to the to- tal.

Previous Total

230,000

BTU

911

20,000

BTU

New Total

250,000

BTU

3.Measure the distance from the gas meter to the cook line. This is the pipe length. Let’s say the pipe length is 40’ (12.2 m) and the pipe size is 1” (2.54 cm).

4.Use the appropriate table to determine the to- tal capacity of your current gas piping.

The total capacity for this example is 320,000 BTU. Since the total required gas pressure, 250,000 BTU is less than 320,000 BTU, the current gas piping will not have to be in- creased.

NOTE: The BTU capacities given in the tables are for straight pipe lengths only. Any elbows or other fittings will decrease pipe capaci- ties. Contact your local gas supplier if you have any questions.

Maximum Capacity of Iron Pipe in Cubic Feet

of Natural Gas Per Hour

(Pressure drop of 0.5 Inch W.C.)

Pipe

 

Nominal Size, Inches

 

Length

 

 

 

 

 

(ft)

3/4”

1”

1-1/4”

1-1/2”

2”

 

 

 

 

 

 

 

 

 

 

 

10

360

680

1400

2100

3950

20

250

465

950

1460

2750

 

 

 

 

 

 

30

200

375

770

1180

2200

 

 

 

 

 

 

40

170

320

660

990

1900

 

 

 

 

 

 

50

151

285

580

900

1680

60

138

260

530

810

1520

70

125

240

490

750

1400

 

 

 

 

 

 

80

118

220

460

690

1300

 

 

 

 

 

 

90

110

205

430

650

1220

 

 

 

 

 

 

100

103

195

400

620

1150

 

 

 

 

 

 

From the National Fuel Gas Code Part 10 Table 10-2

Maximum Capacity of Pipe in Thousands of BTU/hr of Undiluted P.P. Gas at 11” W.C.

(Pressure drop of 0.5 Inch W.C.)

Pipe Length

Outside Diameter, Inches

(ft)

 

 

 

3/4”

1”

1-1/2”

 

 

 

 

 

10

608

1146

3525

20

418

788

2423

 

 

 

 

30

336

632

1946

 

 

 

 

40

287

541

1665

50

255

480

1476

60

231

435

1337

 

 

 

 

70

215

404

1241

 

 

 

 

80

198

372

1144

 

 

 

 

90

187

351

1079

 

 

 

 

100

175

330

1014

From the National Fuel Gas Code Part 10 Table 10-15

11

Page 15
Image 15