Blower Temperature Switch Testing
Blower Temperature Switch Testing (cont’d)
Switch Setting
Opens on rise @ approximately 165oF
Auto resets on fall @ approximately 160oF
Cool switch to
below 160oF
Disconnect wire leads to |
|
|
|
|
| |
switch. Using | N | Replace switch |
| |||
to the ohms setting. Is there |
|
|
| |||
|
| (see page 33). |
| |||
continuity between the switch |
|
|
| |||
|
|
|
|
| ||
terminals? |
|
|
|
|
|
|
Y |
|
|
|
|
|
|
|
|
|
| N |
|
|
Reconnect wire leads and ob- | Y |
|
|
|
| |
serve heater operation. Do |
| Do switch | Y | Exhaust | ||
|
| |||||
exhaust gas temperatures |
|
| contacts |
| temperature | |
rise to or above 170oF with |
|
| open? |
| is too hot. | |
vent connected? |
|
|
|
|
|
|
N |
|
|
|
|
|
|
Do switch con- | Y | Replace switch |
|
| ||
|
|
| ||||
tacts open? |
|
| (see page 33). |
|
|
N
Switch OK
Common causes for high
exhaust temperature
1.Vent length is below mini- mum allowable
2.Vent diameter not to speci- fication
3.Restricted dilution air inlet
4.Missing or deteriorated flue baffle
5.Gas pressure is out of specification
Page 32
32