The Chimney Adapter Kit is a listed alternative venting system for these furnaces. See the kit instructions for complete details.

Canada (and U.S.A.)-This furnace is permitted to be vented into a clay tile-lined masonry chimney that is exposed to the outdoors below the roof line, provided:

1.Vent connector is Type-B double-wall, and

2.This furnace is common vented with at least 1 draft hoodequipped appliance, and

3.The combined appliance input rating is less than the maximum capacity given in Table 8, and

4.The input rating of each space heating appliance is greater than the minimum input rating given in Table 9 for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table 9, and

5.The authority having jurisdiction approves.

If all of these conditions cannot be met, an alternative venting design shall be used, such as the listed chimney adapter kit with a furnace listed for use with the kit, a listed chimney-lining system, or a Type-B common vent.

Inspections before the sale and at the time of installation will determine the acceptability of the chimney or the need for repair and/or (re)lining. Refer to Fig. 35 to perform a chimney inspection. If the inspection of a previously used tile-lined chimney:

a. Shows signs of vent gas condensation, the chimney should be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner, Type-B vent, or a listed chimney adapter kit shall be used to reduce condensation. If a condensate drain is required by local code, refer to the NFGC, Section 10.9 for additional information on condensate drains.

b.Indicates the chimney exceeds the maximum permissible size in the tables, the chimney should be rebuilt or relined to conform to the requirements of the equipment being installed and the authority having jurisdiction.

A chimney without a clay tile liner, which is otherwise in good condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined with a UL listed (ULC listed in Canada) metal liner or UL listed Type-B vent. Relining with a listed metal liner or Type-B vent is considered to be a vent-in-a-chase.

If a metal liner or Type-B vent is used to line a chimney, no other appliance shall be vented into the annular space between the chimney and the metal liner.

Exterior Masonry Chimney FAN + NAT

Installations with Type-B Double-Wall Vent

Connectors ENFPA & AGA

Table 8 – Combined Appliance Maximum Input Rating in

Thousands of BTUH per Hour

VENT HEIGHT

INTERNAL AREA OF CHIMNEY

 

(SQ. IN.)

 

 

(FT)

 

 

 

12

19

 

28

38

 

 

6

74

119

 

178

257

8

80

130

 

193

279

10

84

138

 

207

299

15

NR

152

 

233

334

20

NR

NR

 

250

368

30

NR

NR

 

NR

404

Table 9 – Minimum Allowable Input Rating of Space-Heat-

ing Appliance in Thousands of BTUH per Hour

VENT HEIGHT

 

INTERNAL AREA OF CHIMNEY

 

 

(SQ. IN.)

 

(FT)

 

 

 

 

 

 

 

 

 

 

12

19

 

28

 

38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Local 99% Winter Design

 

 

 

 

 

Temperature: 17 to 26_F

 

 

 

 

 

 

 

 

 

 

 

6

 

 

0

55

 

99

 

141

 

 

 

 

 

 

 

 

 

8

 

 

52

74

 

111

 

154

 

 

 

 

 

 

 

 

 

10

 

 

NR

90

 

125

 

169

 

 

 

 

 

 

 

 

 

15

 

 

NR

NR

 

167

 

212

 

 

 

 

 

 

 

 

 

20

 

 

NR

NR

 

212

 

258

 

 

 

 

 

 

 

 

 

30

 

 

NR

NR

 

NR

 

362

 

 

 

 

 

 

 

 

 

 

 

Local 99% Winter Design

 

 

 

 

 

Temperature: 5 to 16_F*

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

NR

78

 

121

 

166

 

 

 

 

 

 

 

 

 

8

 

 

NR

94

 

135

 

182

 

 

 

 

 

 

 

 

 

10

 

 

NR

111

 

149

 

198

 

 

 

 

 

 

 

 

 

15

 

 

NR

NR

 

193

 

247

 

 

 

 

 

 

 

 

 

20

 

 

NR

NR

 

NR

 

293

 

 

 

 

 

 

 

 

 

30

 

 

NR

NR

 

NR

 

377

 

 

 

 

 

 

 

 

 

 

 

Local 99% Winter Design

 

 

 

 

 

Temperature: ---10 to 4_F*

 

 

 

 

 

 

 

 

 

 

 

6

 

 

NR

NR

 

145

 

196

 

 

 

 

 

 

 

 

 

8

 

 

NR

NR

 

159

 

213

 

 

 

 

 

 

 

 

 

10

 

 

NR

NR

 

175

 

231

 

 

 

 

 

 

 

 

 

15

 

 

NR

NR

 

NR

 

283

 

 

 

 

 

 

 

 

 

20

 

 

NR

NR

 

NR

 

333

 

 

 

 

 

 

 

 

 

30

 

 

NR

NR

 

NR

 

NR

 

 

 

 

 

 

 

 

 

 

 

Local 99% Winter Design

 

 

 

 

Temperature: ---11_F or lower

 

 

 

Not recommended for any vent configuration.

 

 

 

 

 

 

 

 

 

 

*The 99% Winter Design Dry ---Bulb (db) temperatures are found in the 1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and 2 (Canada), or use the 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada).

APPLIANCE APPLICATION REQUIREMENTS

Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, adjusted, and operated properly, the venting system and/or the appliances should not suffer from condensation and corrosion. The venting system and all appliances shall be installed in accordance with applicable listings, standards, and codes.

The furnace should be sized to provide 100% of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air-Conditioning Engineers; or other approved engineering methods. Excessive over-sizing of the furnace could cause the furnace and/or vent to fail prematurely. When a metal vent or metal liner is used, the vent must be in good condition and be installed in accordance with the vent manufacturer’s instructions.

To prevent condensation in the furnace and vent system, the following precautions must be observed:

1.The return-air temperature must be at least 60_F db except for brief periods of time during warm-up from setback at no lower than 55_F (13_C) db or during initial start-up from a standby condition.

2.Adjust the gas input rate per the installation instructions. Low gas input rate causes low vent gas temperatures,

312A

29

Page 29
Image 29
Bryant 120 instruction manual Appliance Application Requirements, Vent Height Internal Area of Chimney

120 specifications

The Bryant 120 is a remarkable system designed for residential and commercial heating and cooling needs, showcasing an impressive blend of efficiency, reliability, and advanced technology. As a part of Bryant's extensive line of HVAC solutions, the Bryant 120 stands out with its features and performance, making it an ideal choice for those seeking comfort year-round.

One of the main features of the Bryant 120 is its exceptional energy efficiency. It boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, enabling homeowners to save on energy costs while enjoying consistent temperature control. This efficiency is aided by its variable-speed compressor, which allows the system to adjust its output based on current requirements, optimizing both energy consumption and comfort.

In terms of technology, the Bryant 120 incorporates advanced controls that enhance user experience and system performance. The system comes equipped with smart thermostats that allow homeowners to monitor and adjust their environment remotely. These thermostats not only provide convenience but also help in optimizing energy usage by learning the household's heating and cooling patterns.

Another characteristic of the Bryant 120 is its durable construction. The unit is built to withstand various weather conditions, featuring a robust cabinet and components designed for longevity. This durability ensures that homeowners can rely on the system for years without the need for frequent repairs or replacements.

Noise levels are also a critical consideration in HVAC systems, and the Bryant 120 addresses this with its quiet operation. The system is designed to minimize sound output, making it suitable for residential areas where noise can be a concern. This is particularly beneficial for nighttime use, providing a comfortable sleeping environment.

Additionally, the Bryant 120 supports eco-friendly refrigerants that comply with environmental standards, contributing to a reduction in greenhouse gas emissions. This commitment to sustainability reflects Bryant's dedication to creating products that are not only effective but also responsible.

Overall, the Bryant 120 encapsulates a harmonious balance of efficiency, advanced technology, durability, and quiet operation. Whether for a new installation or a replacement, the Bryant 120 presents an ideal solution to meet diverse heating and cooling requirements, enhancing comfort while prioritizing energy savings and environmental responsibility.