![Step 3 — Adjustments](/images/new-backgrounds/54348/5434871x1.webp)
Table 10 –
|
|
|
| |
SETUP | SWITCH | NORMAL | DESCRIPTION | |
SWITCH NO. | NAME | POSITION | OF USE | |
|
|
| When OFF, allows | |
Adaptive Heat Mode | OFF | Turn ON when using 2 stage thermostat to allow Low Heat | ||
tion when R to W/W1 closes and High Heat operation when R to | ||||
|
|
| ||
|
|
| W/W1 and W2 close. | |
Blower OFF delay | ON or OFF | Control blower OFF delay time. Used in conjunction with | ||
See Table 14. | ||||
|
|
| ||
Blower OFF delay | ON or OFF | Control blower OFF delay time. Used in conjunction with | ||
See Table 14. | ||||
|
|
|
312A
Step 3 — Adjustments
!WARNING
FIRE HAZARD
Failure to follow this warning could result in injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess
!CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft Furnace input rate must be within
1.Determine the correct gas input rate.
In the U.S.:
The input rating for altitudes above 2,000 ft must be re- duced by 4% for each 1,000 ft above sea level.
For installations below 2000 ft, refer to the unit rating plate.
For installations above 2000 ft, multiply the input on the rating plate by the derate multiplier in Table 11 for the cor- rect input rate.
EXAMPLE:
88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT
|
| Derate |
| Furnace Input Rate |
Furnace Input Rate | X | Multiplier | = | at Installation |
at Sea Level |
| Factor |
| Altitude |
88,000 | X | 0.90 | = | 79,200 |
In Canada: The input rating must be reduced by 10% for altitudes of 2,000 ft to 4,500 ft above sea level by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example and use 0.90 as derate multiplier factor.
2.Determine the correct orifice and manifold pressure adjustment. All models in all positions except Low NOx
models in downflow and horizontal positions use Table 15 (22,000 BTUH per burner).
Table 11 – Altitude Derate Multiplier for U.S.A.
ALTITUDE | % | DERATE MULTIPLIER |
(FT) | OF DERATE | FACTOR* |
0 | 1.00 | |
0.90 | ||
0.86 | ||
0.82 | ||
0.78 | ||
0.74 | ||
0.70 | ||
0.66 | ||
0.62 |
*Derate multiplier factors are based on midpoint altitude for altitude range.
Low NOx models in downflow or horizontal positions MUST use Table 16 (21,000 BTUH per burner). See input listed on rating plate.
a.Obtain average yearly gas heat value (at installed altitude) from local gas supplier.
b.Obtain average yearly gas specific gravity from local gas supplier.
c.Find installation altitude in Table 15 or 16.
d.Find closest natural gas heat value and specific gravity in Table 15 or 16
e.Follow heat value and specific gravity lines to point of intersection to find orifice size and
f.Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
g.Replace orifice with correct size, if required by Table 15 or 16. Use only
EXAMPLE 2:
For 22,000 Btuh per burner application, use Table 15. Heating value = 1000 Btuh/cu ft
Specific gravity = 0.62 Therefore: Orifice No. 43*
Manifold pressure:
*Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
3.Adjust manifold pressure to obtain low fire input rate. (See Fig. 54.)
36