In Canada: Per section 8.24.2 of the
Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturers installation requirements for venting and termination included with the listed mechanical venter.
START-UP, ADJUSTMENT, AND SAFETY
CHECK
Step 1 — General
!WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve if a flame
1.Maintain
2.Make thermostat wire connections at the
3.Gas supply pressure to the furnace must be greater than
!CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
4.Check all
5.Install blower compartment door. Door must be in place to operate furnace.
6.Setup switch descriptions The 2 stage furnace has DIP switches used to select thermostat staging and blower off delay timings. For switch locations on Furnace control board, See Fig. 34 and 58.
7.Setup switch descriptions - See Table 10.
Step 2 — Start-Up Procedures
!WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury, death and/or property damage.
Never purge a gas line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a
1.Purge gas lines after all connections have been made.
2.Check gas lines for leaks.
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death. Blower access door switch opens
3.To Begin Component
Remove blower access door. Disconnect the thermostat R lead from furnace control board. Manually close blower door switch. Short (jumper) the
NOTE: The furnace control allows all components, except the gas valve, to be run for short period of time. This feature helps diagnose a system problem in case of a component failure. Component test feature will not operate if any thermostat signal is present at the control.
Refer to service label attached to furnace or See Fig. 57. Component test sequence is as follows:
a.LED will display previous status code 4 times.
b.Inducer motor starts on
c.Hot surface igniter is energized for 15 sec., then off.
d.Blower motor operates on
e.Blower motor operates on
f.Blower motor operates on COOL speed for 10 sec.
g.Inducer motor goes to
h.Reconnect R lead to furnace control board, remove tape from blower door switch and
4.Operate furnace per instruction on inner door.
5.Verify furnace shut down by lowering thermostat setting below room temperature.
6.Verify furnace restarts by raising thermostat setting above room temperature.
312A
35