Caution!! For the following applications, use the minimum vertical heights as specified below.
For all other applications, follow exclusively the National Fuel Gas Code
|
|
|
|
| |
FURNACE | VENT ORIENTA- | FURNACE IN- | MINIMUM VENT | MINIMUM VERTICAL VENT | |
ORIENTATION | TION | PUT(BTUH/HR) | DIAMETER (IN.)* | HEIGHT (FT)** | |
| Vent elbow left, then | 154,000 |
|
| |
Downflow | 132,000 | 5 | 12 | ||
up Fig. 40 | |||||
|
|
| |||
|
|
|
| ||
Horizontal Left | Vent elbow right, | 154,000 | 5 | 7 | |
then up Fig. 43 | 132,000 | ||||
|
|
| |||
Horizontal Left | Vent Elbow up Fig. | 154,000 | 5 | 7 | |
44 | 132,000 | ||||
|
|
| |||
Horizontal Left | Vent elbow right Fig. | 154,000 | 5 | 7 | |
45 | |||||
|
|
|
| ||
Downflow | Vent elbow up then | 110,000 | 5 | 10 | |
left Fig. 38 | |||||
|
|
|
| ||
Downflow | Vent elbow up, then | 110,000 | 5 | 10 | |
right Fig. 41 | |||||
|
|
|
|
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC. *4 in. inside casing or vent guard **Including 4 in. vent section(s)
312A
A04127
Fig. 49 - Using Tin Snips to Cut Tie Points
!CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
NOTE: Vent connector length for connector sizing starts at furnace vent elbow. The 4 inch vent elbow is shipped for upflow configuration and may be rotated for other positions. Remove the 3 screws that secure vent elbow to furnace, rotate furnace vent elbow to position desired,
The vent connector can exit the door through one of 5 locations on the door.
1.Attach the single wall vent connector to the furnace vent elbow, and fasten the vent connector to the vent elbow with at least two
NOTE: An accessory flue extension KGAFE0112UPH is available to extend from the furnace elbow to outside the furnace casing. If flue extension is used, fasten the flue extension to the vent elbow with at least two
to the flue extension with at least two
2.Vent the furnace with the appropriate connector as shown in Fig.
3.Orient the door to determine the correct location of the door knockout to be removed.
4.Remove the correct
NOTE: A number of techniques can be used to remove these knockouts as seen in Fig. 49 through 53. The knockout in the bottom of the door is unique due to its flanging and is more easily removed by first cutting the two tie points at the edge of the door, using
For the rectangular
For the knockouts in the other locations on the door (top and sides), tin snips can also be used along the door edges; however, the preferred method is to use a hammer and screwdriver to strike a sharp blow (See Fig. 52.) directly to the knockout tie points or use a hammer in the upper left corner of the desired knockout. (See Fig. 53.) Remove any burrs and sharp edges.
NOTE: If a knockout does not come out after two sharp blows, pull and snip as needed to remove the knockout. Additional blows may cause damage to the door.
33