12″ MIN
12″ MIN
VENT PIPE
VENT PIPE
HORIZONTAL TO ROOF | HORIZONTAL TO SIDEWALL |
VENT PIPE
|
|
|
|
|
|
|
|
| 12″ MIN | |
|
|
| 12″ MIN |
|
|
|
|
| (304.8mm) | |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| VENT PIPE | ||
|
|
|
|
|
|
| ||||
|
| (304.8mm) |
|
|
|
| ||||
|
|
|
|
|
|
|
| |||
VERTICAL TO ROOF |
|
|
|
| VERTICAL TO SIDEWALL |
NOTE: A
A96230
Fig. 44 - Short Vent (5 to 8 Ft or 1.5M - 2.4M) System
355CAV
NOTE: Starting at furnace, slope vent pipe a minimum of
VENT TERMINATION
General
Roof termination is preferred since it is less susceptible to damage or contamination, and it has less visible vent vapors. Sidewall termination require sealing or shielding of building surfaces with a corrosive resistance material due to corrosive combustion products of vent system.
NOTE: (Direct
When determining appropriate location for termination, consider the following guidelines:
1.Comply with all clearance requirements stated in Fig. 34 or Fig. 35 per application.
2.Termination or termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equipment.
3.Termination or termination kit should be positioned so that it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves, or light snow.
4.Termination or termination kit should be positioned where it will not be damaged by or subjected to foreign objects such as stones, balls, etc.
5.Termination or termination kit should be positioned where vent vapors are not objectionable.
Extended Exposed Sidewall Pipes
Sidewall combustion air pipe termination (direct
1.Determine combustion air pipe diameter (direct
2.Using winter design temperature (used in load calculations), find appropriate temperature for your application and furnace model.
3.Determine required insulation thickness for exposed pipe length(s).
NOTE: Pipe length(ft) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 6.
37